How to measure insulation resistance and find an interturn short circuit
  1. // ELEKTROPROMREMONT
  2. Insulation resistance

How to measure insulation resistance and find an interturn short circuit

Measuring insulation resistance and finding an interturn short circuit are two different diagnostic operations that are often mistaken for a single test. A megger assesses the insulation between the winding and the frame, between phases, and between electrical circuits of the machine, but it practically cannot reveal a short between neighboring turns of the same coil.

With an interturn defect, the winding can have very high resistance to frame and pass a standard insulation test with flying colors — so "the megger reads fine, but the motor overheats" is a perfectly real situation. Finding an interturn short calls for different methods: comparing phase resistances, measuring inductance, a surge test, phase-current analysis, thermal imaging.

Reliable diagnostics must answer two separate questions: does the winding have adequate insulation to frame and to the other phases, and is there a short inside the winding itself, between its turns?

What insulation resistance is, and what a megger shows

Insulation resistance describes an insulation system’s ability to resist current flow between a conductor and other electrically separated parts. In a motor, insulation is checked winding-to-frame, phase-to-phase, stator-winding-to-rotor-winding, and across other electrical circuits.

A megger applies a DC test voltage and measures a very small leakage current made up of a capacitive component, an absorption component, a surface leakage component, and a component through any defective areas. Readings are often lower at first and climb gradually as the winding’s capacitance charges and polarization processes proceed in the insulation.

What a megger does not show

A megger cannot reliably reveal a short between neighboring turns, a wrong turn count, a shorted part of a coil, a weak interturn insulation that only breaks down under an impulse voltage, or asymmetry between parallel branches.

With an interturn short, both shorted turns stay insulated from the frame — no leakage path to ground appears, so the megger reading can stay high despite the defect being present.

What an interturn short circuit is and why it happens

An interturn short circuit is an electrical contact between turns of the same coil or winding that should normally be separated by insulation. Even a few shorted turns form a closed loop of very low resistance in which a large circulating current is induced — causing local overheating, damage to the insulation of neighboring turns, and a worsening defect.

The main causes are insulation aging, winding overheating, overload, frequent or prolonged starts, running at reduced voltage, phase imbalance, VFD supply, transient overvoltages, contamination, moisture, mechanical vibration, loosened slot wedges, or repair defects.

Possible symptoms include the motor heating up quickly, one phase drawing more current, humming, rising vibration, reduced power and lower starting torque. With one or two shorted turns, the change in a phase’s resistance can be very small, so an ordinary multimeter often misses the defect.

Preparing to measure insulation resistance

Fully disconnect the motor, lock out re-energizing, and verify there is no voltage present. Before connecting the megger, disconnect the power cable, the variable frequency drive, the soft starter, any capacitors and electronic sensors — a megger must never be connected to the output of a drive or other power electronics.

Inspect and clean the terminal box — a contaminated or damp box can significantly lower the result even when the winding itself is sound. If the three-phase winding has six leads brought out, it is best to remove the links and check each phase separately, to frame and phase-to-phase.

Choosing the test voltage

The test voltage is chosen based on the motor’s rated voltage, insulation class, condition and age, the manufacturer’s instructions, and the plant’s internal procedures. In practice, low-voltage motors are often tested with a 500 V DC megger, while higher voltage classes use 1000 V, 2500 V or other levels — the choice should never come from a single rule of thumb.

Sensors, encoders, thermistors and other low-voltage auxiliary circuits need much lower test voltages — an excessive voltage can damage weakened insulation.

Insulation resistance measurement sequence

  1. 01Record the winding and air temperature — insulation resistance depends heavily on temperature, so comparing uncorrected results is misleading.
  2. 02Run a brief pre-check — confirm there is no direct short circuit, all electronics are disconnected, and the frame is solidly grounded.
  3. 03Apply the test voltage and watch the reading for the set time — a value at 60 seconds is commonly recorded.
  4. 04Record a stable value, not just the first figure after applying voltage — large windings have significant capacitance, so readings can keep changing for a while.
  5. 05Remove the test voltage following the instrument’s instructions.
  6. 06Discharge the winding — it can retain a dangerous charge, so it must be reliably grounded and given enough time, especially for large and high-voltage machines.

The absorption ratio and the polarization index

The absorption ratio shows how insulation resistance changes over the first minute of the test — readings at 60 and 15 seconds, or 60 and 30 seconds, are compared. If the insulation is dry and shows strong polarization properties, resistance typically rises over time; a low ratio can point to moisture, contamination or aging, though the figure should be interpreted carefully.

The polarization index is the ratio of resistance at 10 minutes to resistance at 1 minute. It is more often used for large, high-voltage and critical machines — it helps assess moisture, contamination and the overall condition of the bulk insulation, but it is not a universal criterion for every modern insulation system.

A single measurement can be misleading — the trend is the most informative: results after manufacture, after repair, previous scheduled measurements, and the current value.

Interpreting and localizing low insulation resistance

A low reading can be caused by moisture, contamination, carbon or metallic dust, oil, damaged leads, a dirty terminal box, a slot insulation breakdown, or thermal aging. Before concluding a rewind is needed, the source of the leakage must be localized.

  1. 01Disconnect the supply cable from the motor and test the cable separately.
  2. 02Test the motor separately without the cable.
  3. 03Remove the phase links and check each phase.
  4. 04Clean and dry the terminal box.
  5. 05Disconnect sensors, heaters and auxiliary circuits.
  6. 06Repeat the measurement; if needed, disassemble the motor and test the winding directly.

If a low reading is caused by moisture, drying can significantly improve the result — methods include a drying oven, a reduced-voltage current, an induction method, or hot air, with temperature and insulation resistance monitored throughout. If resistance does not recover after drying, an actual insulation defect, not just moisture, is likely.

How to search for an interturn short circuit

Since a megger is poorly suited to this task, a combination of other methods is used.

01

Comparing phase resistances

For small resistances, the resistance of test leads and contacts can be comparable to the winding’s own resistance, so a four-wire (Kelvin) method is preferred, separating the current-supply loop from the voltage-sensing loop. Phases can only be compared at the same temperature, in the same scheme, and accounting for parallel branches — an interturn short usually lowers resistance slightly, while an open parallel branch, conversely, can raise it.

02

Measuring inductance

An interturn short changes not just resistance but the coil’s magnetic properties too — the effective turn count drops, inductance falls, and losses rise. An LCR meter or a dedicated analyzer can show a difference between phases even when resistances are nearly equal, but the rotor must be in the same position for every measurement.

03

A surge test

A short high-voltage pulse is applied to the winding — its inductance and the tester’s capacitance form an oscillating circuit, and the instrument records the shape of the decaying wave. Three phases are compared to each other, matching coils are compared, or a current curve is compared to a reference. An interturn short changes the oscillation frequency, amplitude, decay rate and symmetry against the other phases — this is one of the most effective methods for finding interturn defects, but a wrongly chosen voltage can damage a weakened winding.

04

A reduced AC voltage test and the voltage-drop method

Another method is applying the same reduced AC voltage to each phase and comparing currents: a phase with an interturn short may draw more current and heat up faster. The voltage-drop method is useful for low-resistance windings, armatures and pole coils — the same test current is passed through them and the voltage drop is measured.

05

Phase current and current-spectrum analysis

An interturn short can cause unequal phase currents, but a raised current in one phase can also result from voltage imbalance, a poor contact, rotor damage, or mechanical overload — so current asymmetry alone cannot be taken as proof of a stator defect. Current spectrum analysis can reveal electrical asymmetry and characteristic changes in harmonic content, and works best as part of a broader diagnostic.

06

Thermal imaging and magnetic diagnostics

Under a reduced test voltage, or during operation, a defective area may heat up faster — a thermal camera can pick out a locally hot coil or a bad joint, though the winding may be hidden by the frame and a short test may show only a small difference. For large machines, pole coils and armatures, induction sensors and search coils are also used to monitor magnetic flux.

Diagnostic table

Test resultLikely causeNext step
Low resistance on every phase to frameMoisture or general contaminationClean, dry, retest
Low resistance on one phase to frameA local phase defectSeparate and localize
High resistance to frame, but unequal currentsInterturn defect, supply, or rotorResistances, inductances, a surge test
One phase’s resistance is lowerAn interturn short or a connection errorCheck inductance and run a surge test
One phase’s resistance is higherAn open branch or a poor contactCheck the connections
One phase’s inductance is lowerShorted turnsRun a surge test
One phase draws more currentA winding defect or voltage imbalanceMeasure voltages and winding parameters
Megger reading rises after dryingMoistureFinish drying and retest
Resistance stays low after dryingInsulation damageDisassembly and repair

When the motor must not be switched on

  • a direct winding-to-frame breakdown;
  • low and unstable insulation resistance;
  • signs of carbon tracking or significant phase asymmetry;
  • a confirmed interturn short circuit;
  • rapid local overheating, smoke, or the smell of burnt insulation;
  • deformed end windings or loosened coils;
  • protection tripping repeatedly, or a sharp rise in one phase’s current.

Common diagnostic mistakes

  • measuring without disconnecting the power cable, or connecting the megger to a variable frequency drive;
  • choosing the wrong test voltage and not controlling temperature;
  • recording only the instant reading without discharging the winding afterward;
  • testing phases without removing the links, or ignoring a dirty terminal box;
  • searching for an interturn short with a megger alone;
  • using a multimeter on a very low-resistance winding;
  • ignoring rotor position when measuring inductance;
  • not comparing to historical data, and continuing to run after local overheating is found.

Frequently asked questions

Will a megger show an interturn short circuit?

Usually not. It checks insulation to frame and between electrically separated circuits, not between adjacent turns of the same coil.

Why does the motor overheat if insulation resistance is normal?

Possible causes include an interturn short, overload, rotor damage, incorrect supply, or a cooling problem.

Which instrument finds an interturn short circuit?

A surge tester is the most informative. A milliohmmeter, an LCR meter, current analysis and thermal analysis are also used.

Can a multimeter find an interturn short circuit?

Only for a gross defect — one or a few shorted turns often produce no noticeable change on an ordinary multimeter.

Can a megger be connected to a variable frequency drive?

No. The motor and cable must be disconnected from the power electronics as the equipment’s instructions require.

Does low resistance always mean a rewind is needed?

No. The cause can be moisture, contamination, the cable, or the terminal box.

Does drying help with an interturn short circuit?

No, not once an electrical contact has already formed between turns. Drying only helps with moisture.

Insulation system diagnostics

EPR (Elektropromremont) performs comprehensive diagnostics, repair and testing of insulation systems in industrial electric machines.

The scope of work includes:

  • measuring insulation resistance, the absorption ratio and the polarization index;
  • measuring phase resistances with the four-wire method;
  • measuring inductance and surge-testing windings;
  • finding interturn short circuits and localizing frame breakdowns;
  • testing individual coils, wound rotors, armatures and field windings;
  • thermal imaging diagnostics and drying windings;
  • local insulation repair, coil replacement and full rewinding;
  • dielectric strength testing and report preparation.

Important disclaimer

This material is for informational purposes. The values, diagnostic methods, scope of work and recommendations given here are general and do not replace the manufacturer’s technical documentation. The final decision for a specific machine is made from its own diagnostics and inspection, taking into account its type, power, design, duty, operating history and applicable standards.

Need your winding checked?

We measure insulation resistance, search for an interturn short circuit with a surge test, and carry out a complete winding assessment with a test report.

Get a consultation